Publication Details

Evaluation of the Touch Voltage Recorded in the Compensated Network 22 kV During Earth Fault

TOPOLÁNEK David, ORSÁGOVÁ Jaroslava, TOMAN Petr, DVOŘÁK Jaromír and ŠÁTEK Václav. Evaluation of the Touch Voltage Recorded in the Compensated Network 22 kV During Earth Fault. In: Proceeding of the 13th International Scientific Conference Electric Power Engineering 2012. Brno: Faculty of Electrical Engineering and Communication BUT, 2012, pp. 159-164. ISBN 978-80-214-4514-7.
Czech title
Vyhodnocení dotykových napětí zaznamenaných v kompenzované síti 22kV během zemního spojení
Type
conference paper
Language
english
Authors
Topolánek David, doc. Ing., Ph.D. (FEEC BUT)
Orságová Jaroslava, Ing. (UEEN FEEC BUT)
Toman Petr, Ing. (UEEN FEEC BUT)
Dvořák Jaromír (FEEC BUT)
Šátek Václav, Ing., Ph.D. (DITS FIT BUT)
Keywords

touch voltage, earth fault, compensated distribution network, residual current

Abstract

The paper focuses on the evaluation of the touch voltage measured during a series of experimental measurements performed in a compensated 22 kV distribution network equipped with an automatic system for the additional earthing of the affected phase. During the experiment, a metallic earth fault was artificially created in selected distribution transforming substations. Two different network extents were tested, a basic one - 300 A - considered by Czech technical standards as a limit value for operating a mixed distribution network and an extent of 800 A representing a maximum value of the tested network. The paper analyses the level of touch voltage with respect to the technical standards in force as well as with respect to the voltage of the increase of the substation potential during the fault for 300 A and 800 A and assesses the influence of the additional earthing of the affected phase on the level of touch voltage.

Published
2012
Pages
159-164
Proceedings
Proceeding of the 13th International Scientific Conference Electric Power Engineering 2012
Conference
Electric Power Engineering 13th Scientific Conference, Brno, CZ
ISBN
978-80-214-4514-7
Publisher
Faculty of Electrical Engineering and Communication BUT
Place
Brno, CZ
UT WoS
000321966500027
BibTeX
@INPROCEEDINGS{FITPUB10083,
   author = "David Topol\'{a}nek and Jaroslava Ors\'{a}gov\'{a} and Petr Toman and Jarom\'{i}r Dvo\v{r}\'{a}k and V\'{a}clav \v{S}\'{a}tek",
   title = "Evaluation of the Touch Voltage Recorded in the Compensated Network 22 kV During Earth Fault",
   pages = "159--164",
   booktitle = "Proceeding of the 13th International Scientific Conference Electric Power Engineering 2012",
   year = 2012,
   location = "Brno, CZ",
   publisher = "Faculty of Electrical Engineering and Communication BUT",
   ISBN = "978-80-214-4514-7",
   language = "english",
   url = "https://www.fit.vut.cz/research/publication/10083"
}
Back to top